PID logic sim for a HVAC VAV box
This file contains hidden or bidirectional Unicode text that may be interpreted or compiled differently than what appears below. To review, open the file in an editor that reveals hidden Unicode characters.
Learn more about bidirectional Unicode characters
class VavBoxController: | |
''' | |
TODO add in - | |
state machines for sensor reliability | |
air flow PID control for damper | |
integral windup prevention | |
occupancy state for unoc setpoints | |
''' | |
def __init__( | |
self, | |
deadband=5, | |
space_temp_setpoint=72, | |
heat_min_flow=100, | |
heat_max_flow=850, | |
cool_min_flow=100, | |
cool_max_flow=1000, | |
satisfied_airflow_setpoint=50, | |
ahu_sat=55, | |
max_dat=90, | |
vav_air_flow_volume=0, | |
# heating PID params | |
Kp_heating = 5, | |
Ki_heating = 1.0, | |
Kd_heating = 0, | |
integral_heating = 0, | |
prev_error_heating = 0, | |
# cool PID params | |
Kp_cooling = 5, | |
Ki_cooling = 1.0, | |
Kd_cooling = 0, | |
integral_cooling = 0, | |
prev_error_cooling=0, | |
): | |
self.deadband = deadband | |
self.heat_min_flow = heat_min_flow | |
self.heat_max_flow = heat_max_flow | |
self.cool_min_flow = cool_min_flow | |
self.cool_max_flow = cool_max_flow | |
self.satisfied_airflow_setpoint = satisfied_airflow_setpoint | |
# AHU Supply Air Temperature | |
self.ahu_sat = ahu_sat | |
# Maximum Discharge Air Temperature | |
self.max_dat = max_dat | |
# Degrees Fahrenheit | |
self.space_temp_setpoint = space_temp_setpoint | |
# heating PID params | |
self.Kp_heating = Kp_heating | |
self.Ki_heating = Ki_heating | |
self.Kd_heating = Kd_heating | |
self.integral_heating = integral_heating | |
self.prev_error_heating = prev_error_heating | |
# cool PID params | |
self.Kp_cooling = Kp_cooling | |
self.Ki_cooling = Ki_cooling | |
self.Kd_cooling = Kd_cooling | |
self.integral_cooling = integral_cooling | |
self.prev_error_cooling = prev_error_cooling | |
def update_setpoint(self, space_temp_setpoint): | |
self.space_temp_setpoint = space_temp_setpoint | |
def calc_cooling_pid(self, error, dt=1): | |
self.integral_cooling += error * dt | |
derivative = (error - self.prev_error_cooling) / dt | |
output = (self.Kp_cooling * error) + (self.Ki_cooling * self.integral_cooling) + (self.Kd_cooling * derivative) | |
self.prev_error_cooling = error | |
return output | |
def calc_heating_pid(self, error, dt=1): | |
self.integral_heating += error * dt | |
derivative = (error - self.prev_error_heating) / dt | |
output = (self.Kp_heating * error) + (self.Ki_heating * self.integral_heating) + (self.Kd_heating * derivative) | |
self.prev_error_heating = error | |
return output | |
def control_logic(self, space_temp, dt=1): | |
mode = "Satisfied" | |
heating_demand = 0 | |
cooling_demand = 0 | |
# Calculate the error or deviation from setpoint | |
error = self.space_temp_setpoint - space_temp | |
# If error is within the deadband, | |
# system is satisfied; no action needed | |
if abs(error) > self.deadband / 2: | |
if error > 0: | |
# Heating needed | |
mode = "Heating" | |
heating_demand = self.calc_heating_pid(error, dt) | |
else: | |
# Cooling needed | |
mode = "Cooling" | |
# Cooling demand uses -error to make it positive | |
cooling_demand = self.calc_cooling_pid(-error, dt) | |
# Limit the demands to a maximum of 100% | |
heating_demand = max(min(heating_demand, 100), 0) | |
cooling_demand = max(min(cooling_demand, 100), 0) | |
else: | |
# Satisfied: Use satisfied airflow setpoint | |
airflow_setpoint = self.satisfied_airflow_setpoint | |
dat_setpoint = self.ahu_sat | |
return mode, dat_setpoint, airflow_setpoint, heating_demand, cooling_demand | |
# Update DAT setpoint and airflow based on mode | |
if mode == "Heating": | |
dat_setpoint = self.ahu_sat + ( | |
heating_demand * (self.max_dat - self.ahu_sat) / 100 | |
) | |
airflow_setpoint = self.heat_min_flow + ( | |
heating_demand * (self.heat_max_flow - self.heat_min_flow) / 100 | |
) | |
elif mode == "Cooling": | |
dat_setpoint = self.ahu_sat | |
airflow_setpoint = self.cool_min_flow + ( | |
cooling_demand * (self.cool_max_flow - self.cool_min_flow) / 100 | |
) | |
# Ensure the airflow is within the bounds | |
airflow_setpoint = max( | |
min(airflow_setpoint, self.heat_max_flow), self.heat_min_flow | |
) | |
dat_setpoint = max( | |
min(dat_setpoint, self.max_dat), self.ahu_sat | |
) | |
return mode, dat_setpoint, airflow_setpoint, heating_demand, cooling_demand | |
def simulate(): | |
vav = VavBoxController() | |
# Constant temperature to test cooling and PID integral effect. | |
satisfied_temp = 73 # within dead band | |
constant_cooling_temp = 76 | |
constant_heating_temp = 68 | |
steps = 30 | |
print("\nTesting Heating Demand with Constant Temperature outside Deadband") | |
for step in range(10): | |
current_temp = constant_heating_temp | |
mode, dat_setpoint, airflow_setpoint, heating_demand, cooling_demand = vav.control_logic(space_temp=current_temp) | |
print(f"************* STEP: {step+1} *************") | |
print(f"Zone Temp = {current_temp:.2f}F, Zone Setpoint = {vav.space_temp_setpoint}F") | |
print(f"Mode = {mode}, DAT Setpoint = {dat_setpoint:.2f}F, Airflow Setpoint = {airflow_setpoint}") | |
print(f"Heating PID = {heating_demand:.2f}%, error = {vav.prev_error_heating:.2f}, integral = {vav.integral_heating:.2f}") | |
print(f"Cooling PID = {cooling_demand:.2f}%, error = {vav.prev_error_cooling:.2f}, integral = {vav.integral_cooling:.2f}") | |
print("\nTesting Satisfied Mode within Deadband") | |
for step in range(5): | |
current_temp = satisfied_temp | |
mode, dat_setpoint, airflow_setpoint, heating_demand, cooling_demand = vav.control_logic(space_temp=current_temp) | |
print(f"************* STEP: {step+1} *************") | |
print(f"Zone Temp = {current_temp:.2f}F, Zone Setpoint = {vav.space_temp_setpoint}F") | |
print(f"Mode = {mode}, DAT Setpoint = {dat_setpoint:.2f}F, Airflow Setpoint = {airflow_setpoint}") | |
print(f"Heating PID = {heating_demand:.2f}%, error = {vav.prev_error_heating:.2f}, integral = {vav.integral_heating:.2f}") | |
print(f"Cooling PID = {cooling_demand:.2f}%, error = {vav.prev_error_cooling:.2f}, integral = {vav.integral_cooling:.2f}") | |
print("\nTesting Cooling Demand with Constant Temperature outside Deadband") | |
for step in range(5, steps): | |
current_temp = constant_cooling_temp | |
mode, dat_setpoint, airflow_setpoint, heating_demand, cooling_demand = vav.control_logic(space_temp=current_temp) | |
print(f"************* STEP: {step+1} *************") | |
print(f"Zone Temp = {current_temp:.2f}F, Zone Setpoint = {vav.space_temp_setpoint}F") | |
print(f"Mode = {mode}, DAT Setpoint = {dat_setpoint:.2f}F, Airflow Setpoint = {airflow_setpoint}") | |
print(f"Heating PID = {heating_demand:.2f}%, error = {vav.prev_error_heating:.2f}, integral = {vav.integral_heating:.2f}") | |
print(f"Cooling PID = {cooling_demand:.2f}%, error = {vav.prev_error_cooling:.2f}, integral = {vav.integral_cooling:.2f}") | |
simulate() |